| Sign In | Join Free | My bjjsgy.com | 
              
  | 
      
Brand Name : PEPPERL FUCHS
Model Number : KFD2-UT2-1
Place of Origin : Germany
MOQ : 1
Price : Negotiable
Payment Terms : T/T
Supply Ability : 100pcs per month
Delivery Time : Negotiable
Packaging Details : carton
Manufacturer : PEPPERL FUCHS
Product No : KFD2-UT2-1
Current range : 0 ... 20 mA or 4 ... 20 mA
Lead resistance : max. 50 Ω per line
Types of measuring : 2-, 3-, 4-wire connection
Connection side : field side
Power dissipation : ≤ 0.98 W
PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink or source mode
General specifications
 Signal type    Analog input
 Functional safety related parameters
 Safety Integrity Level (SIL)    SIL 2
 Supply
 Connection    terminals 14+, 15- or power feed module/Power Rail
 Rated voltage    20 ... 30 V DC
 Ripple    within the supply tolerance
 Power dissipation    ≤ 0.98 W
 Power consumption    max. 0.98 W
 Interface
 Programming interface    programming socket
 Input
 Connection side    field side
 Connection    terminals 1, 2, 3, 4
 RTD    type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
 type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
 type Cu10, Cu50, Cu100 (P50353-92)
 type Ni100 (DIN 43760)
 Measuring current    approx. 200 µA with RTD
 Types of measuring    2-, 3-, 4-wire connection
 Lead resistance    max. 50 Ω per line
 Measurement loop monitoring    sensor breakage, sensor short-circuit
 Thermocouples    type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
 type L (DIN 43710: 1985)
 type TXK, TXKH, TXA (P8.585-2001)
 Cold junction compensation    external and internal
 Measurement loop monitoring    sensor breakage
 Potentiometer    0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
 Voltage    selectable within the range -100 ... 100 mV
 Input resistance    ≥ 1 MΩ (-100 ... 100 mV)
 Output
 Connection side    control side
 Connection    output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-)
 Output    Analog current output
 Current range    0 ... 20 mA or 4 ... 20 mA
 Fault signal    downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
 Source    load 0 ... 550 Ω
 open-circuit voltage ≤ 18 V
 Sink    Voltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V,
 series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage.
 The maximum value of the resistance is (V - 5)/0.0215 Ω.
 Transfer characteristics
 Deviation    
 After calibration    Pt100: ± (0.06 % of measurement value in K + 0.1 % of span + 0.1 K (4-wire connection))
 thermocouple: ± (0.05 % of measurement value in °C + 0.1 % of span + 1 K (1.2 K for types R and S)) , includes ± 0.8 K fault of the cold junction compensation (CJC)
 mV: ± (50 µV + 0.1 % of span)
 potentiometer: ± (0.05 % of full scale + 0.1 % of span, (excludes faults due to lead resistance))
 Influence of ambient temperature    Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔTamb*)
 thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔTamb*)), influence of cold junction compensation (CJC) included
 mV: ± (0.01 % of measurement value + 0.006 % of span)/K ΔTamb*)
 potentiometer: ± 0.006 % of span/K ΔTamb*)
 *) ΔTamb = ambient temperature change referenced to 23 °C (296 K)
 Influence of supply voltage    < 0.01 % of span
 Influence of load    ≤ 0.001 % of output value per 100 Ω
 Reaction time    worst case value (sensor breakage and/or sensor short circuit detection enabled)
 mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s

| 
                                             | 
                
                        2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode Images |